Product · HVAC engineering

HVAC engineering, sized on your plan.

Airflows, air changes and heat loads are calculated room by room from your layout and zoning. The ducts are routed from your air handling units, sized and checked, and the fan power gives a first energy cost.

  • ACH
  • m³/h
  • Heat loads
  • HEPA
  • Ducts
PharmaTwin editor: HVAC airflow and duct model of a cleanroom facility
What you can do

Built for pharma, step by step.

  • 01

    Airflows and air changes

    Each room's supply airflow comes from its air change rate (ACH) and its volume, net of pillars. The ACH follows the grade by default and stays editable.

  • 02

    Air balance with the zoning

    The exhaust of each room is its supply minus the air leaking through its doors at the GMP pressures. A room that leaks more than it receives is flagged.

  • 03

    Heat and moisture loads

    Heating and cooling loads of the supply air, plus the heat of the personnel and of the equipment placed in each room, and the moisture they release.

  • 04

    Units, ducts and energy

    Fan filter units or HEPA terminals laid out on each ceiling, ducts routed from the AHUs and sized for the target velocity, pressure drop, fan power and yearly energy cost.

How it works

How the HVAC is calculated

Standard engineering methods, step by step. The formulas and every constant are one click away in the editor, and settings such as velocities or energy prices can be changed per project.

  1. 01

    Supply airflow

    The airflow is the air change rate times the net volume of the room. Default rates follow the grade.

  2. 02

    Air balance

    What a room doesn't extract leaks through its doors: that is what holds its pressure above its neighbours.

  3. 03

    Thermal loads

    Sensible load of the supply air at standard air properties, plus internal gains.

  4. 04

    Ceiling units

    Grade A and B rooms get fan filter units by default, other rooms ducted HEPA terminals. Units that don't fit the ceiling are flagged.

  5. 05

    Duct sizing and pressure drop

    Each section is sized for the target velocity and rounded to standard sizes, then its pressure drop follows Darcy-Weisbach, with the Swamee-Jain friction factor.

  6. 06

    Fan power and energy

    The fans are sized on the most demanding path. The yearly cost uses your operating hours and electricity price.

Related features

Goes hand in hand with

  • HVAC checked

    Air changes, air balance with door leakage, ceiling units, duct sizes and velocities.

  • GMP zoning checked

    Pressure cascades, airlocks, grade changes and containment, checked at every door.

  • 1,000+ equipment library

    Real pharma equipment, with its dimensions, heat gain and GMP data.

FAQ

Frequently Asked Questions

How are air change rates calculated?

For each room, the supply airflow is its air change rate times its volume net of pillars. The default rate follows the grade (360 for A and B, 60 for C, 25 for D) and can be changed room by room.

Are equipment heat gains included?

Yes. Equipment from the library carries its heat gain, which is added to the cooling load of the room it is placed in, with 0.1 kW per person.

How are the ducts sized?

Each section is sized for a target velocity (6 m/s by default) within the ceiling void, and its pressure drop is calculated with Darcy-Weisbach. The fans are sized on the most demanding path.

Can the HVAC results be exported?

Yes. They appear in the PDF feasibility report and in the Excel exports.

Ready to modernize your facility design?

Join leading pharmaceutical companies, CDMOs, and engineering firms using PharmaTwin.